Instructions on installation of HYDROFLAME cast-in-place sleeves

(1) Select the correct sleeve for pipe type, size and concrete thickness. Align the hatch marks on lower base to layout lines on form deck to center the sleeve for the pipe that will penetrate through. Attach sleeve to deck using the nail holes provided in the lower base. Make sure the protective cap is securely inserted in the sleeve top before pouring concrete.

(2) Pour the concrete slab around the device to the appropriate slab thickness.

(3) As the form deck is removed after the appropriate concrete curing time has been accomplished, the nails can be pulled through the nail slots on the base, as designed. Remove the protective cap from the top portion of the device before inserting pipe.

(4) Cut the inside diameter of the protective cap from the top portion of the device before inserting the pipe.

(5) Prior to installation, thoroughly clean the outside of the pipe to be inserted through the sleeve. The pipe must be free of concrete, dirt, paint, rust and or anything protruding from the outside of pipe including burrs of pipe material. Make sure the mid-body seal membrane is clean of all debris, dirt, concrete or anything that might of gotten on the mid-body seal membrane during or after construction that could damage the sealing surface of the mid-body seal membrane when the pipe is inserted through the mid-body seal. Failure to perform proper cleaning could damage the mid-body seal membrane of the sleeve when the pipe is installed. Note: Presealed Systems is not responsible for sleeve performance when installation instructions are not followed.

(6) After cleaning debris from the surface of the pipe of choice, it can now be inserted through the device.

Recommended (1): Insert the pipe of choice up through the bottom of the device. Note: If circumstances arrive in the field, you may insert the pipe of choice down through the top of the device. Care should be taken to avoid coming in contact with the top of the fire ring tabs that hold the fire material in place in the lower section of the device. Recommended (2): Use the factory end of cast iron or steel pipe to be inserted through the device, if not the cast iron or steel pipe shall have a slight bevel applied to the end of pipe being inserted through the sleeve to ease installation and minimize the possibility of damaging the mid-body seal membrane. 2) Use a compatible soap solution or other recommended compatible lubricant to ease installation and further minimize the possibility of damaging the mid-body seal membrane. Lightly coating the mid-body seal center sealing surface will ease the insertion of pipe.

Note: Not for use In Walls

Safety & Precautions

Keep this device out of reach of children
Read the Material & Safety Data Sheet

Storage of Device

Store in a covered or closed area protected from weather
Do not stack devices on top of one another other than how they are shipped from manufacture